Activity
From 10/31/2021 to 11/29/2021
11/26/2021
- 10:57 AM Feature #1845 (Resolved): 泰雷兹ats接口对接
- 1.通道建立成功,列车数据对方无法提供
2.cios数据推送,全数据对点正确。
3.cios不提供火警故障状态以及电网未知态状态
4.提供现场抓包 - 10:51 AM Feature #1845 (Resolved): 泰雷兹ats接口对接
- 2021/11/25日 周四9:00,在C3通号网管室,跟泰雷兹ATS 对接ats接口
11/23/2021
11/19/2021
- 10:03 AM Feature #1824 (New): L17 PSCADA徐盈路信号消缺
- 10:02 AM Feature #1823 (New): L05 肖塘主变定值组消缺
- 10:01 AM Feature #1822 (New): L07 PSCADA 南陈路、新村主编、上海大学、场中路消缺
- 09:59 AM Feature #1821 (New): L05 PSCADA颛桥电力新增调试
- 09:59 AM Feature #1820 (New): L09 CIOS系统调试
- 09:58 AM Feature #1819 (New): L07 PSCADA消缺
- 09:58 AM Feature #1818 (New): L05 PA接口调试
- 09:57 AM Feature #1817 (New): L17 PSCADA徐盈路消缺
- 09:57 AM Feature #1816 (New): L05 PSCADA肖塘主变、环城东路、颛桥消缺
- 09:56 AM Feature #1815 (New): C3 大楼网闸信号对接
- 09:55 AM Feature #1814 (New): L07 FAS陈太路停车场对点
- 09:54 AM Feature #1813 (New): L05 PSCADA莘庄、东川、北桥消缺
- 09:53 AM Feature #1812 (New): L05 PACADA银都新增点位调试
11/15/2021
- 09:30 AM Feature #1798 (Resolved): 6-8-11换乘站 东方体育中心 AFC、cctv客流分析 接口调试
- 1.现场实际报文与提供文档不同,与18号线AFC解析文档相同,使用相应协议后解析反馈正确。 使用网口,端口为提供的错误文档中说的 9000 端口,现场测试实际应网转串-串转网后连接,但由于对方相关网转串仪器安装失败无法使用,暂时使用网...
- 09:20 AM Feature #1798 (Resolved): 6-8-11换乘站 东方体育中心 AFC、cctv客流分析 接口调试
- 时间:20211112 13:00到达
人员:陆静科(负责)+熊心
地点:东方体育中心站
采用协议:东体AFC协议、cctv客流分析协议
11/01/2021
- 03:25 PM Feature #1760: 6-8-11换乘站 东方体育中心 测试tdsi门禁接口
- 上传现场抓包 可以分析超时原因
- 10:00 AM Feature #1760 (Resolved): 6-8-11换乘站 东方体育中心 测试tdsi门禁接口
- 针对现场使用测试结果,总结如下:
1.依据对方点表查看反馈功能正常
2.控制功能实际与文档不符,实际使用标准mdbus16号功能码组包格式进行下控(文档中为15号)已修改代码
3.对门下控命令为寄存器第8位 不是第0位 即下控... - 09:47 AM Feature #1760 (Resolved): 6-8-11换乘站 东方体育中心 测试tdsi门禁接口
- 时间:20211029 9:00到达
人员:陆静科(负责)+吴萸峰
地点:东方体育中心站
采用协议:东体ACS门禁协议
根据对方厂家配合接通协议并根据实际情况对代码进行修改满足需求,并编译FEP版本