数据处理每个RTU的点数统一成UINT16
Start date:
05/09/2020
Due date:
% Done:
100%
Estimated time:
Defect version:
Description
部分代码使用了short类型来处理点号,实际造成只能处理32767个点。
改成UINT16后,可支持65535个点(但点号65535 不允许使用,用作-1)
数据库需要更改:
TB4009_DIGPOINT.F4009_POINTNO1 smallint -> int
TB4009_DIGPOINT.F4009_POINTNO2 smallint -> int
TB4007_ANAPOINT.F4007_POINTNO smallint -> int
TB4014_ACCPOINT.F4014_POINTNO smallint -> int
Related issues
History
Updated by xiangyang li over 4 years ago
- Related to Feature #475: 单个RTU设备采集的遥信、遥测数要求能支持到65535 added
Updated by xiangyang li over 4 years ago
- Status changed from In Progress to Resolved