Project

General

Profile

Bug #528

bin2.2.3sp2测试:控制点无实际对应的遥信点时,依然会判拒控

Added by Hanqing Liu over 4 years ago. Updated over 4 years ago.

Status:
Closed
Priority:
Normal
Assignee:
Target version:
Start date:
04/27/2020
Due date:
% Done:

100%

Estimated time:
Defect version:

Description



Files

微信图片_20200427105537.png (9.27 KB) 微信图片_20200427105537.png Hanqing Liu, 04/27/2020 10:56 AM
微信图片_20200427105546.png (71 KB) 微信图片_20200427105546.png Hanqing Liu, 04/27/2020 10:56 AM

History

#1

Updated by xiangyang li over 4 years ago

  • Project changed from ISCS需求及问题 to ISCS#FEP
  • Assignee set to xiangyang li
  • Target version set to 2.2.3 sp2
#2

Updated by xiangyang li over 4 years ago

  • Status changed from New to In Progress

目前实时库中点号使用了无符号16位整数,造成设置的-1,实际上变成了65535。 目前2.2.3版本简单处理下,使用65535来判断。

#3

Updated by xiangyang li over 4 years ago

  • Status changed from In Progress to Resolved
  • % Done changed from 0 to 100
#4

Updated by xiangyang li over 4 years ago

  • Status changed from Resolved to Closed

Also available in: Atom PDF