Bug #528
bin2.2.3sp2测试:控制点无实际对应的遥信点时,依然会判拒控
Start date:
04/27/2020
Due date:
% Done:
100%
Estimated time:
Defect version:
Description
Files
History
Updated by xiangyang li over 4 years ago
- Project changed from ISCS需求及问题 to ISCS#FEP
- Assignee set to xiangyang li
- Target version set to 2.2.3 sp2
Updated by xiangyang li over 4 years ago
- Status changed from New to In Progress
目前实时库中点号使用了无符号16位整数,造成设置的-1,实际上变成了65535。 目前2.2.3版本简单处理下,使用65535来判断。
Updated by xiangyang li over 4 years ago
- Status changed from In Progress to Resolved
- % Done changed from 0 to 100