Project

General

Profile

Bug #3479

15CISCS的QTISCS304R4-modbus_TRAIN_c.dll协议出现tcp链路假活释放不掉

Added by yufeng wu 4 months ago. Updated 4 months ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Start date:
09/11/2024
Due date:
% Done:

0%

Estimated time:

Description

项目:3C-15CISCS
版本:QTISCS304R4
软件:modbus_TRAIN_c.dll
事件:20240911凌晨QTISCS的2台冗余服务器ip 91.1和91.2,没有任何切换动作,主域控、主auth、主dac、主daq都在91.1上
采集atsFEP的RTU ip91.7win杀fepdaq.exe主进程停机,切换到备机ip91.8变为主
但是在91.1内netstat查看7003端口链路与91.7还保持ESTABLISHED,91.7内netstat查看7003端口链路已经不存在了
导致91.1无法切换去找备机91.8握手7003端口


Files

Modbus_TRAINc.cpp (5.47 KB) Modbus_TRAINc.cpp yufeng wu, 09/11/2024 05:22 PM
modbus_TRAIN_c.dll (90.5 KB) modbus_TRAIN_c.dll yufeng wu, 09/11/2024 05:22 PM
modbus_TRAIN_c-304-202409111741.dll (90 KB) modbus_TRAIN_c-304-202409111741.dll yufeng wu, 09/11/2024 06:18 PM

History

#1

Updated by yufeng wu 4 months ago

  • File Modbus_TRAINc.cpp added

20*6=120秒无数据接收,自动断开tcp链路

#2

Updated by yufeng wu 4 months ago

  • File deleted (Modbus_TRAINc.cpp)
#3

Updated by yufeng wu 4 months ago

收到有效数据后,pLink->RegisterFrm(FRAME_RX_SUC);终止link出错6次计数

#4

Updated by yufeng wu 4 months ago

采用研发发布的20240911-1741版本,已提交电科现场-胡,15CISCS-ats今晚临修点使用

Also available in: Atom PDF