Bug #2599

5号线现场报回,ehmi控制电力开关失败,点预置按扭后,执行按钮还是灰的,60秒后出现超时提示

Added by shixun yan about 2 years ago. Updated about 2 years ago.

Status:
Resolved
Priority:
Normal
Assignee:
shixun yan
Target version:
Start date:
09/29/2022
Due date:
% Done:

100%

Estimated time:
Defect version:

Description

按抓包信息来看,控制服务器已经将返校信息返回,但是ehmi没有收到.
现在在ehmi增加一些log,判断是什么原因导致ehmi收不到返校的消息.


Files

Log0929.7z (148 KB) Log0929.7z shixun yan, 09/29/2022 01:49 PM

History

#1

Updated by shixun yan about 2 years ago

#2

Updated by shixun yan about 2 years ago

  • Status changed from New to In Progress
#3

Updated by shixun yan about 2 years ago

  • Status changed from In Progress to Resolved
  • % Done changed from 0 to 100

查看log分析出来的原因,在做完一键停送电以后,有时候管道会出现异常,留下很多消息,如果这时候切控制框做控制,按1秒一次的频率,
我们是拿不到返校返回的消息.所以libctrldlg这边修改一下,如果读到的消息不是自己这个点的,立刻再读一次管道.