Project

General

Profile

Feature #211

当控制点无实际对应的遥信点时,遥控不判拒控不报拒控

Added by yufeng wu over 5 years ago. Updated about 4 years ago.

Status:
Closed
Priority:
Normal
Assignee:
Target version:
Start date:
07/22/2019
Due date:
% Done:

100%

Estimated time:
Defect version:

Description

对于有些控制点(如复位),没有对应的实际遥信点,因此不能判断控制结果是否成功,只能认为命令下发就是成功的。因此界面及报警中不希望出现拒控的消息。
DO表中设置【执行时间限】为0,或者对应的遥信点的采集序号1和采集序号2都设置为-1,则认为此控制点不需要判断结果。


Files

History

#1

Updated by xiangyang li almost 5 years ago

  • Subject changed from 当控制点代码对应的DI表内的点无效-1时,遥控不判拒控不报拒控 to 当控制点无实际对应的遥信点时,遥控不判拒控不报拒控
  • Assignee set to xiangyang li
  • Target version set to 2.2.3 sp2
#2

Updated by xiangyang li almost 5 years ago

  • Description updated (diff)
  • Status changed from New to In Progress
#3

Updated by xiangyang li almost 5 years ago

  • Description updated (diff)
#4

Updated by xiangyang li almost 5 years ago

  • Status changed from In Progress to Resolved
  • % Done changed from 0 to 100
#5

Updated by xiangyang li over 4 years ago

  • Status changed from Resolved to In Progress
#6

Updated by xiangyang li over 4 years ago

  • Status changed from In Progress to Resolved
#7

Updated by xiangyang li about 4 years ago

  • Status changed from Resolved to Closed

Also available in: Atom PDF