Feature #2031
fep-ha 虚拟点转发逻辑及相关规约修改
Defect version:
Description
fep-ha双活是备机的采集为假活状态,但虚拟点逻辑认为备机的采集通道连通,导致大平台出现同一rtu两个通道都连通状态,逻辑不符;
104c,104s规约运行在拔掉网线后无法自主切换
修改
fep-ha修改
1.fep-ha虚拟点逻辑修改,默认备机的采集通道状态为0;
2.由于测试孤岛及恢复时,发现会出现大平台展示的虚拟点数据与redis中存储的虚拟点不匹配且fep-ha无法判断不匹配,只能等待总召匹配,
将虚拟点变化转发改为周期转发以保证大平台与fep-ha数据一致;
规约修改
104s,104c在规约内部新增设置超时机制来允许rtu切换通道;
History
Updated by pengfei xu almost 3 years ago
- Status changed from In Progress to Resolved
- % Done changed from 0 to 100
- Estimated time set to 8.00 h