Bug #2005
SH-L15-3C电力转发FEP程序崩溃
Start date:
02/14/2022
Due date:
02/15/2022
% Done:
100%
Estimated time:
Defect version:
Description
查找发现 winFEP版se104s规约崩溃,由于FEP没有配置电度点,而大平台配置了电度总召时间;se104s规约关于电度总召的处理有问题(没有判断出FEP没配电度点而获取电度数据)导致规约崩溃;
修改:增加判断电度总召时判断电度数量;
检查了FEP的sefeps规约,此规约处理了电度总召的电度数量问题;
检查了FEP-HA的sefeps,se104s规约,也都处理了电度总召的电度数量问题;
History
Updated by pengfei xu almost 3 years ago
- Status changed from In Progress to Resolved
- % Done changed from 0 to 100