Project

General

Profile

Bug #1910

南昌三QTISCS304的电调ehmi一键停送电插件停电+单控-执行命令超时-重启电调工作站sys守护后恢复20211219凌晨

Added by yufeng wu over 2 years ago.

Status:
New
Priority:
Normal
Assignee:
-
Start date:
12/20/2021
Due date:
% Done:

0%

Estimated time:

Description

南昌三QTISCS304的电调ehmi一键停送电插件停电+单控-执行命令超时-重启电调工作站sys守护后恢复20211219凌晨
实时事项显示,返校正确与预置发令间隔时间较长,记录报10s,40s,60s,80s
实际DO配置返校超时时间15s
wireshark抓包显示车站FEPdebian8回答返校都是1秒内
抓包和日志记录在服务器\\192.168.2.250\upload\M03南昌\现场备份\QTISCS304一键停送电故障20211219
em_css问题?


Related issues

Related to ISCS需求及问题 - Bug #2621: SHL05CIOS设备调遥控偶尔会出现返校正确消息很慢50几秒才返回到ehmi的单操遥控窗或者超60s直接超时禁止点执行按钮Resolved10/10/2022

Actions

History

#1

Updated by yufeng wu over 1 year ago

  • Related to Bug #2621: SHL05CIOS设备调遥控偶尔会出现返校正确消息很慢50几秒才返回到ehmi的单操遥控窗或者超60s直接超时禁止点执行按钮 added

Also available in: Atom PDF