南昌三QTISCS304的电调ehmi一键停送电插件停电+单控-执行命令超时-重启电调工作站sys守护后恢复20211219凌晨
Status:
New
Priority:
Normal
Assignee:
-
Start date:
12/20/2021
Due date:
% Done:
0%
Estimated time:
Description
南昌三QTISCS304的电调ehmi一键停送电插件停电+单控-执行命令超时-重启电调工作站sys守护后恢复20211219凌晨
实时事项显示,返校正确与预置发令间隔时间较长,记录报10s,40s,60s,80s
实际DO配置返校超时时间15s
wireshark抓包显示车站FEPdebian8回答返校都是1秒内
抓包和日志记录在服务器\\192.168.2.250\upload\M03南昌\现场备份\QTISCS304一键停送电故障20211219
em_css问题?
Related issues
History
Updated by yufeng wu about 2 years ago
- Related to Bug #2621: SHL05CIOS设备调遥控偶尔会出现返校正确消息很慢50几秒才返回到ehmi的单操遥控窗或者超60s直接超时禁止点执行按钮 added