Bug #1788
电力104规约采集遥测值时排除正负无穷值和无效值
Start date:
11/10/2021
Due date:
11/11/2021
% Done:
100%
Estimated time:
1.00 h
Defect version:
Description
现象:采集值正负“(+/-)1.#INF00”不会影响系统处理,但非数字(NaN)“-1.#IND00”写入实时库AI点表analog中后会导致后续采集的AI值不能再写入analog中
解决:采集端即电力104规约采集后的AI值是正负无穷值和非数字(无效值)时不再上传给ISCS系统,打印一个log作为提示
Files
Related issues
History
Updated by pengfei xu about 3 years ago
- Due date set to 11/11/2021
- % Done changed from 0 to 100
- Estimated time set to 1.00 h
Updated by xiangyang li about 3 years ago
- Related to Bug #1784: SHL15 dac处理服务器analog实时库接收电力AI溢出坏值-4194304后,当ehrawdc采集到好值更新上来后,analog的对应值僵死-1.#IO不能更新好值(ehdc显示-1.#IND00,ananlog显示-1.#IO) added