Project

General

Profile

Bug #1788

电力104规约采集遥测值时排除正负无穷值和无效值

Added by jiwei shi almost 3 years ago. Updated almost 3 years ago.

Status:
Resolved
Priority:
Normal
Assignee:
Target version:
Start date:
11/10/2021
Due date:
11/11/2021
% Done:

100%

Estimated time:
1.00 h
Defect version:

Description

现象:采集值正负“(+/-)1.#INF00”不会影响系统处理,但非数字(NaN)“-1.#IND00”写入实时库AI点表analog中后会导致后续采集的AI值不能再写入analog中
解决:采集端即电力104规约采集后的AI值是正负无穷值和非数字(无效值)时不再上传给ISCS系统,打印一个log作为提示


Files

无效值.jpg (353 KB) 无效值.jpg jiwei shi, 11/10/2021 08:13 PM

Related issues

Related to ISCS需求及问题 - Bug #1784: SHL15 dac处理服务器analog实时库接收电力AI溢出坏值-4194304后,当ehrawdc采集到好值更新上来后,analog的对应值僵死-1.#IO不能更新好值(ehdc显示-1.#IND00,ananlog显示-1.#IO)Resolved11/09/2021

Actions

History

#1

Updated by pengfei xu almost 3 years ago

  • Status changed from New to In Progress
#2

Updated by pengfei xu almost 3 years ago

  • Due date set to 11/11/2021
  • % Done changed from 0 to 100
  • Estimated time set to 1.00 h
#3

Updated by xiangyang li almost 3 years ago

  • Target version set to FEP_V3.0.5
#4

Updated by pengfei xu almost 3 years ago

  • Status changed from In Progress to Resolved
#5

Updated by xiangyang li almost 3 years ago

  • Related to Bug #1784: SHL15 dac处理服务器analog实时库接收电力AI溢出坏值-4194304后,当ehrawdc采集到好值更新上来后,analog的对应值僵死-1.#IO不能更新好值(ehdc显示-1.#IND00,ananlog显示-1.#IO) added

Also available in: Atom PDF