Project

General

Profile

Feature #1430

L09CIOSC3侧备自投功能消缺及故障消缺

Added by jy Wang about 3 years ago. Updated about 3 years ago.

Status:
Resolved
Priority:
Normal
Assignee:
Start date:
06/04/2021
Due date:
06/05/2021
% Done:

100%

Estimated time:
3.00 h
Spent time:

Description

施工内容:,1、小南门备自投测试,只验证小南门备自投的遥信信号,不验证功能,无需变电站配合单(站内配合转换备自投
信号并确认),调试期间会重启CIOS服务器,期间设备调度、行调、调度长席位CIOS相关业务(CCTV、PA、EMCS、FAS、电
力)无法使用,需站内监控,施工结束后恢复正常运行。


Files

History

#1

Updated by jw Gao about 3 years ago

小南门备自投35kV分段备自投信号与遥控功能均正常,400V分段站内设备拒动因新华无人配合无法验证。

#2

Updated by jw Gao about 3 years ago

  • Status changed from New to Resolved

Also available in: Atom PDF