Bug #1356
ehdbo更改di点的采集号后,dcdebug变位原采集号仍产生告警
Start date:
04/25/2021
Due date:
% Done:
100%
Estimated time:
Defect version:
Description
一个DI点采集号是1,更改为2后,变dcdebug的2号点不起作用,变1号点产生告警;
History
Updated by jiwei shi over 3 years ago
情形2:车站1的DI点a使用车站2的RTU,采集号109,车站2仍有采集号为109的DI点b;此时把点a采集号通过ehdbo改为-1,dcdebug变位109号点,告警仍然产生2条;
Updated by jiwei shi over 3 years ago
- Status changed from New to Resolved
- % Done changed from 0 to 100
ehdbo修改DI点采集号后,刷新实时库表DiIOList不生效,去除代码中多余的字符"SEMODEL."后刷新实时库成功;