Description

需要先向五防系统进行遥控预置,成功后向PSCADA系统发送预置、执行命令,预置成功后自动执行,不需要人工介入;
广州项目对应的五防规约:gzwf104c 由于公共地址需要填写车站号,因此控制点号按照 【车站号*256+控制点】的原则填写,由对应规约进行处理。
ehmi针对五防控制提供单独的控制对话框,发送五防检查时的类型填写CSI_K_FIVECHECK,收到返校成功后,下发的遥控命令类型填写CSI_K_SELECT_EXECUTE (表示调度员执行一次,后台自动进行选择并执行)
DO参数库及实时库增加五防系统的RTU和PointNo字段:
参数库:F4011_CHECKRTUNO (smallint),F4011_CHECKPOINTNO(smallint)
实时库:CheckRtuNo,CheckPointNo 类型2


Files

五防点表.xlsx (13.4 KB) 五防点表.xlsx zhixue wei, 03/08/2021 02:25 PM

History

#1

Updated by xiangyang li almost 4 years ago

  • Status changed from New to In Progress
#2

Updated by xiangyang li almost 4 years ago

  • Description updated (diff)
#3

Updated by xiangyang li almost 4 years ago

  • Description updated (diff)
#4

Updated by xiangyang li almost 4 years ago

  • Description updated (diff)
#5

Updated by zhixue wei almost 4 years ago

ehdbo的DO点表里面五防控制点号的配置规则:五防系统提供的站号*256+(五防系统提供的设备点号-24576)

#7

Updated by xiangyang li almost 4 years ago

  • Status changed from In Progress to Resolved
  • % Done changed from 0 to 100