Project

General

Profile

Feature #1207

SHL15 FEP debian8 v3.02 se104c协议设备回答返校正确07慢15秒导致 转发se104s 5s时回答QTISCS 返校错误--需修改超时判断参数默认20s或可设置

Added by yufeng wu almost 4 years ago. Updated 16 days ago.

Status:
Resolved
Priority:
High
Assignee:
Start date:
01/20/2021
Due date:
01/23/2021
% Done:

100%

Estimated time:

Description

SHL15 FEP debian8 v3.02 se104c协议 测试能耗接口遥控
QTISCS向FEP发送遥控,FEP的转发RTU se104s收到遥控预置后,FEP的采集RTU se104c 立即向华立发送遥控预置命令06,正确
5秒后,华立没有回答返校正确,15s才回答se104c返校正确07,且期间一直有变化要测回答给我们fep
5秒FEP的转发RTU se104s 回答QTISCS 47 否定返校错误,导致ehmi界面无法继续发送执行遥控执行命令

遥控抓包在服务器位置sftp://transafer.cn/upload/M15/接口/EMS/0118_TCL_遥控返校错误.cap
希望20210123 SHL15正式开通对外运营前,调整完成

History

#1

Updated by xiangyang li almost 4 years ago

设置se104c的超时时间,可解决此问题

#2

Updated by jy Wang 16 days ago

  • Status changed from New to Resolved
  • Assignee set to jy Wang
  • % Done changed from 0 to 100

已修复该问题

Also available in: Atom PDF